KINGSINE K68i Overcurrent Relay Test Three-Phase Protection Relay Tester

Categories Relay Test System
Brand Name: KINGSINE
Model Number: K68i
Certification: CE/ISO9001
Place of Origin: China
MOQ: 1 set
Price: Negotiation
Payment Terms: L/C,T/T
Supply Ability: 100 sets/month
Delivery Time: 15 working days
  • Haven't found right suppliers
  • Our buyer assistants can help you find the most suitable, 100% reliable suppliers from China.
  • And this service is free of charge.
  • we have buyer assistants who speak English, French, Spanish......and we are ready to help you anytime!
  • Submit Buying Request
    • Product Details
    • Company Profile

    KINGSINE K68i Overcurrent Relay Test Three-Phase Protection Relay Tester

    The Most Cost-effective, Best field testing convenience in whole of the world
    3x35A & 4x300V independent high burden and accuracy output channels
    Lightweight, <20.5Kg
    Inbuilt 6.4” True color TFT LCD display, keyboard and rotary encoder, fully control without laptop
    Advance software testing modules for optional
    3-Years guarantee of free repair and life-long maintenance
    Free software upgrade

    7 Channels (4x300V & 3x35A) outputs, Each output channels are independent and simultaneous control of magnitude, Phase angle and frequency values, able to inject DC, AC sine wave and up to 20x harmonics.
    Variable battery simulator, DC 0-300V, 120Watts max.
    Quick relay testing facility in Manual mode
    Switch on to fault test(SOTF)
    GPS sync end-to-end testing
    Online Vector display
    Automatic test report creation
    Anti-clipping detect, Wrong wiring connect alarm and self-protect, overload and overheat protection

    Basic functions:
    DC test
    AC test
    Distance relay test
    Harmonic test
    Frequency test
    8 pairs binary inputs
    4 pairs binary outputs

    Advance software functions (optional for selections):
    Differential test
    State sequence test
    Time characteristic test
    Advance distance test
    Synchronizer test
    Fault recurrence (fault play back)



    Type of relays can be tested:
    Items ANSI® No.
    Distance protection relay 21
    Synchronising or synchronism-check relays 25
    Undervoltage relays 27
    Directional Power relays 32
    Undercurrent or underpower relays 37
    Negative sequence overcurrent relays 46
    Overcurrent/ground fault relays 50
    Inverse time overcurrent/ground fault relays 51
    Power factor relays 55
    Overvoltage relays 59
    Voltage or current balance relays 60
    Directional overcurrent relays 67
    Directional ground fault relays 67N
    DC overcurrent relays 76
    Phase-angle measuring or out-of-step protection relays 78
    Automatic reclosing devices 79
    Frequency relays 81
    Motor overload protection relays 86
    Differential protection relays 87
    Directional voltage relays 91
    Voltage and power directional relays 92
    Tripping relays 94
    Voltage regulating relays
    Overimpedance relays, Z>
    Underimpedance relays, Z
    Time-delay relays

    Voltage Outputs
    Output Range & Power 4×300 V ac (L-N) 120 VA max each
    300 V dc (L-N) 120 W max each
    Accuracy ±2mV @ <2V ac
    <0.12%Rd+0.05Rg Typ. @ 2~300V ac
    <0.07%Rd+0.03Rg Guar. @ 2~300V ac
    ±10mV @ <5V dc
    ±0.5% @ ≥5V dc
    Voltage Range Range I : 30V
    Range II : 300V
    Automatic Range
    DC Offset <10mV Typ./ <60mV Guar
    Resolution 1mV
    Distortion <0.015%Typ. / <0.05% Guar.
    Current Outputs
    Output Range & Power 3×35A ac (L-N) 450 VA max each
    105A ac (3L-N) 1200 VA max
    3×20A dc (L-N) 300W max each
    Accuracy ±1mA @ <0.5A ac
    <0.15%Rd+0.05Rg Typ. @ 0.5A~35A ac
    <0.07%Rd+0.03Rg Guar. @ 0.5A~35A ac
    ±5mA @ <1A dc
    ±0.5% @ ≥1A dc
    Current Range Range I: 3A
    Range II: 35A
    Automatic Range
    DC Offset <3mA Typ./ <10mA Guar
    Resolution 1mA
    Distortion <0.025%Typ. / <0.07% Guar.
    Frequency & Phase Angle
    Frequency Range DC, 5~1000Hz
    Frequency Accuracy ±1ppm @ 5~65Hz
    ±10ppm @ 65~450Hz
    ±20ppm @ 450~1000Hz
    Frequency Resolution 0.001 Hz
    Phase Range -360°~360°
    Phase Accuracy <0.05° Typ. / <0.1° Guar. 50/60Hz
    Phase Resolution 0.001°
    Aux. DC Voltage Source (Battery simulator)
    Range 0~300V @ 120W max
    Accuracy 0.5%Rg Guar.
    Binary Input
    Quantity 8pairs
    Type wet/dry, up to 300Vdc max input
    Time resolution 100us
    Sampling Rate 10KHz
    Debounce time 0~25ms (Software Controlled)
    Time range 999.999s
    Time errors ±1ms @ 1s, ±0.1% @ >1s
    Galvanic isolation Isolated as 1,2,3,4-8 pairs
    Binary Output (Relay Type)
    Quantity 4pairs
    Type Potential free relay contacts, software controlled
    Break Capacity AC Vmax: 400Vac / Imax:4A / Pmax:1000VA
    Break Capacity DC Vmax: 300Vdc / Imax:4A / Pmax:300W
    Synchronization
    Synchronization Mode  External GPS (Optional)
    Power supply & Environment
    Nominal Input Voltage 110V/220/230V ac, appointed, ±15%
    Permissible Input Voltage 85~264Vac, 125~350VDC, auto-protective
    Nominal Frequency 50/60Hz
    Permissible Frequency 45Hz~65Hz
    Power Consumption 1500 VA max
    Connection Type Standard AC socket 60320
    Operating Temperature -10℃~55℃
    Storage Temperature -20℃~70℃
    Humidity <95%RH, non-condensing
    Others
    PC Connection RJ45 Ethernet, 10/100M
    Grounding Terminal 4mm banana socket
    Weight 20.5 Kg
    Dimensions(W x D x H) 360×450×140(mm)
    Quality KINGSINE K68i Overcurrent Relay Test Three-Phase Protection Relay Tester for sale
    Send your message to this supplier
     
    *From:
    *To: Kingsine Electric Automation Co., Ltd.
    *Subject:
    *Message:
    Characters Remaining: (0/3000)
     
    Find Similar Products By Category:
    Inquiry Cart 0