JJZ-FF Overhead Line Fault Indicator is usually used in 5~38KV overhead line
power distribution network to monitor and detect short-circuit and earth fault. The fault is
indicated by mechanical flag and three ultra-bright blinking LEDs with 360 sight.
The indicator can be mounted under live conditions with the help of an adapter and a
hot stick.
Contact Supplier Chat Online Diana
  • Overview
  • Datasheet
  • Download
  • Related Products
  • Related Solutions
JJZ-FF Overhead Line Fault Indicator is usually used in 5~38KV overhead line power distribution network to monitor and detect short-circuit and earth fault. The fault is
indicated by mechanical flag and three ultra-bright blinking LEDs with 360 sight.The indicator can be mounted under live conditions with the help of an adapter and a
hot stick. The trip current and reset time can be set by dial switches during production.And battery low voltage warning can be distinguished and indicated by red mechanical
flag.

Features
Short circuit Fault:Red mechanical flag and three red ultra-bright blinking LEDs.
Earth-fault:Red mechanical flag and three red ultra-bright blinking LEDs
Low Battery Warning: Red mechanical flag.
Parameter Adjust:The parameters can be adjusted by dial switches during production.
Power Supply:Lithium battery, type AA 2.7Ah/3.6V.
parameter
Subject Value
Short-circuit Trip Current (Phase to Phase) 150A, 300A, 450A, 600A, can be set by dial switch during production
Trip Current Delay 40, 80, 120, 200ms, can be set during production
Indication Unit Reset
  1. Manual by magnet
  2. Time reset: adjustable, 2 minutes, 8h, 24h, 48h, can be set during production
  3. Auto reset after repower, 30s default, only for permanent fault
Protection Class IP68
Internal Type Test According to IEEE495-2007
Operation
Temperature Range
-40~+70℃
Power Supply Lithium battery type AA 3.6V/2.7Ah, replaceable
Battery Life 10 years
Weight Approx. 600g
Dimensions